AX-01, AX-02, Features and Technical Specifications
Input Power Voltage : 240 V ac rms ± 10 %
Frequency : 50/60 HZ
Output Power Voltage : 95 V dc at 240 V a.c. input
Current : 6 Amps dc
    8 Amps for 10 secs for motor starting
Field Resistance : 10 Ohms, minimum
Build up : Less than 5V a.c. rms at AVR power input terminals
Regulation : ±1% of set voltage
Voltage Adjustment : ±10% over 415 V
Stability Adjustment : Adjustable to get stable operation and desired response
Voltage Sensing : 415 V a.c. two line sensing. AVR senses average of the generator wave form.
Response time : less than 75 milli seconds.
Under frequency Protection
(FRO)
: Adjustable from 40Hz to 60Hz
Parallel Operation Facility
(QDC) (in AX-02 model)
: Adjustable droop up to 6%. 5A.CT Signal from 'W phase to be connected to terminal Q1 & Q2
Circuit Protection : Protection against voltage transients by L-C networks and high energy suppressors.
RFI Suppression : AVR includes RFI filters to filter out the RFI generated due to power device turn-on
Temperature drift : Typically 0.025% per degree celcius over operating temperature range.
Fuse : 4 amps fuse provided inside the AVR box.
Operating temperature : -20°C to + 60° C ambient
Power dissipation : 10 watts (max)
Size (LBH) (mm); : AX01 :140x125x40
AX02:140x145x45
Weight : AX01 : 600 gms
AX02 : 700 gms
     