| Input Power Voltage |
: |
240 V ac rms ± 10 % |
| Frequency |
: |
50/60 HZ |
| Output Power Voltage |
: |
95 V dc at 240 V a.c. input |
| Current |
: |
6 Amps dc |
| |
|
8 Amps for 10 secs for motor starting |
| Field Resistance |
: |
10 Ohms, minimum |
| Build up |
: |
Less than 5V a.c. rms at AVR power input terminals |
| Regulation |
: |
±1% of set voltage |
| Voltage Adjustment |
: |
±10% over 415 V |
| Stability Adjustment |
: |
Adjustable to get stable operation and desired response |
| Voltage Sensing |
: |
415 V a.c. two line sensing. AVR senses average of the generator wave form. |
| Response time |
: |
less than 75 milli seconds. |
Under frequency Protection (FRO) |
: |
Adjustable from 40Hz to 60Hz |
Parallel Operation Facility (QDC) (in AX-02 model) |
: |
Adjustable droop up to 6%. 5A.CT Signal from 'W phase to be connected to terminal Q1 & Q2 |
| Circuit Protection |
: |
Protection against voltage transients by L-C networks and high energy suppressors. |
| RFI Suppression |
: |
AVR includes RFI filters to filter out the RFI generated due to power device turn-on |
| Temperature drift |
: |
Typically 0.025% per degree celcius over operating temperature range. |
| Fuse |
: |
4 amps fuse provided inside the AVR box. |
| Operating temperature |
: |
-20°C to + 60° C ambient |
| Power dissipation |
: |
10 watts (max) |
| Size (LBH) (mm); |
: |
AX01 :140x125x40 AX02:140x145x45 |
| Weight |
: |
AX01 : 600 gms AX02 : 700 gms |
| |
|
|